AS/NZS 3000 Earth Conductor Size Calculator

Minimum Earth Conductor Size Calculator

Enter the active conductor details

How this calculator works

The calculator uses the largest active conductor supplying the part of the installation being protected and returns the minimum protective earthing conductor size from AS/NZS 3000:2018 Table 5.1.

Reference table

Active size (mm²)With copper active (mm²)With aluminium active (mm²)
!

Important limitations and notes

  • Educational design aid only. It does not replace the Wiring Rules, engineering judgement, product instructions, or regulatory requirements.
  • This calculator is for the protective earthing conductor sizing lookup in AS/NZS 3000:2018, Table 5.1. It is not a calculator for the bonding conductors, MEN connection, or earth electrode sizing.
  • The 1 mm² and 1.5 mm² copper earth sizes shown in AS/NZS 3000:2018, Table 5.1 have a specific application restriction: they may only be used where incorporated in a multicore cable or flexible cord, subject to AS/NZS 3000:2018, Clause 5.3.3.4.
  • A larger conductor may be required to satisfy the fault-current/disconnection-time requirements of AS/NZS 3000:2018, Clause 5.3.3.1.1. This calculator does not perform that adiabatic verification.
  • Always check the current edition of the Standard, applicable amendments, local regulatory requirements, cable manufacturer’s data and the actual installation conditions before selecting the final conductor size.
  • A larger earthing conductor may be required after considering the earth-fault current, disconnection time, fault-loop impedance, installation arrangement and other applicable requirements.