Maximum Fault-Clearing Time Calculator

Cable protection

Cable short-circuit calculator

Calculate fault-clearing time, permissible fault current or minimum conductor size using the cable short-circuit withstand equation.

Fault-clearing formula

t = (K² × S²) / I²
t time in seconds K conductor constant S area in mm² I fault current in A

Enter cable details

Conductor inputs

All fields required
What do you want to calculate?
Conductor material

The supplied Table 5.1 does not provide an aluminium K value at the 350 °C limit for high-temperature insulation.

Temperature reference

Insulation limits used by the calculator

The insulation type determines the permitted final conductor temperature. The selected temperatures and conductor material then determine K.

160°C

Thermoplastic

For conductors up to and including 300 mm². The limit is 140 °C for conductors larger than 300 mm².

250°C

Cross-linked elastomeric

R-EP-90, R-CPE-90, R-HF-90, R-CSP-90, R-HF-110 and R-F-110.

250°C

Cross-linked polyolefin

X-90, X-90UV, X-HF-90 and X-HF-110.

350°C

High temperature

R-S-150 and Type 150 fibrous insulation.

Table 3.1 — Limiting temperatures for insulated cables (Normal use conductor temperature)
Type of cable insulation123
Thermoplastic
V-7575750
HFI-75-TP, TPF-757575-20
V-9075900
HFI-90-TP, TP-907590-20
V-90HT751050
Cross-linked elastomeric
R-EP-909090-40
R-CPF-90, R-HF-90, R-CSP-909090-20
R-HF-110, R-F-110110110h
R-S-150150150-50
Cross-linked polyolefin (XLPE)
X-90, X-90UV, X-HF-909090h
X-HF-110110110h
Mineral-insulated metal-sheathed (MIMS)
MIMS100 (sheath)250 (sheath)–
Other types
PE, LLDPE7070h
Type 150 fibrous or polymeric150150–
Table 5.2 — Temperature limits for insulating materials in contact with conductors
MaterialTemperature limit, °C
Thermoplastic
I.I.DPE, PE, V-75, IIHF-75-TP, TPE-75, V-90, IIHF-90-TP, TP 90 and V-90IIHT
≤ 300 mm²160
> 300 mm²140
Cross-linked elastomeric
R-FP-90, R-CPF-90, R-IIHF-90, R-CSP-90, R-IIHF-110 and R-F-110250
Cross-linked polyolefin
X-90, X-90IIJV, X-IIHF-90 and X-IIHF-110250
High temperature
R-S-150 and Typc 150 fibrous350
Table 5.1 — Values of constant (K) for determination of permissible short-circuit currents
Initial
°C
Copper Aluminium Lead Steel
140150160220250350 140150160250 150200 150200
13037.152.263.5106.0120.4155.124.634.542.079.69.617.318.934.2
12545.658.568.8109.3123.3157.330.238.745.581.610.718.021.235.5
11065.274.883.1118.8131.8164.143.249.555.087.213.719.927.239.4
9085.492.999.7131.0142.9173.156.661.666.194.617.122.433.844.2
8589.997.1103.6134.0145.6175.459.664.368.696.417.823.035.345.4
8094.3101.2107.4136.9148.3177.762.567.071.298.218.623.536.846.6
7598.5105.1111.2139.9151.1179.965.369.773.7100.019.324.138.347.7
70102.7109.0114.8142.8153.8182.268.072.276.1101.820.024.739.748.9
65106.7112.8118.4145.7156.5184.570.774.878.5103.620.725.341.150.0
60110.6116.5122.0148.6159.2186.873.377.280.9105.421.425.842.551.2
55114.5120.2125.5151.6161.9189.275.979.783.2107.222.126.443.952.3
50118.3123.9129.0154.5164.7191.578.482.185.5109.022.727.045.253.4
45122.1127.4132.5157.3167.4193.880.984.587.8110.923.427.546.554.6
40125.8131.0135.9160.2170.1196.283.486.990.1112.724.128.147.955.7
35129.4134.5139.3163.1172.8198.685.889.292.4114.524.728.649.256.8
30133.1138.0142.7166.0175.6200.988.391.594.6116.325.429.250.558.0
25136.7141.5146.0168.9178.3203.390.793.996.9118.126.029.851.859.1
Final conductor temperature (°C) shown in header columns.
Note: The results represent the cable short-circuit withstand relationship only. Confirm the final cable and protective-device selection against all applicable installation, derating, voltage-drop and disconnection requirements.

Fault Time · Cable short-circuit withstand calculator

Values reproduced from the supplied Tables 5.1 and 5.2.